Gateway V4 + M-Bus over RS-485
Wireless M-Bus Gateway V4 with the wired M-Bus add-on over an RS-485 interface.
This is a variant of the Gateway V4 + M-Bus. It connects to wired M-Bus through an external RS-485 level converter (e.g. Relay PW100) instead of a native M-Bus master interface. Hardware type and firmware are the same (LOB-GW4-MBUS); only the M-Bus connection differs.
Description
Gateway for remote reading of wireless and wired MBus values via NB-IoT, LTE-M mobile radio or LoRaWAN to the Internet. Suitable for indoor and weather-protected outdoor installation. This product variant uses an external M-Bus level converter (e.g. Relay PW100) connected via RS-485. The gateway itself does not provide a native M-Bus master interface. Instead, communication with wired M-Bus meters is performed via:
- Gateway (RS-485) → External Level Converter (e.g. PW100) → M-Bus line
- From a configuration perspective, the setup is identical to the standard GW4-MBus firmware variant, see Gateway V4 + M-Bus.
Features
- wM-Bus meter data upload via NB-IoT or LTE-M mobile radio (2FF / Mini SIM card)
- Secure DTLS data transmission (client + server certificates) via mobile radio
- Connection via CoAP and DTLS (NB-IoT, LTE-M) or MQTT (LTE-M) to the Lobaro platform
- Direct connection via MQTT (LTE-M) to third-party systems possible.
- Alternative upload via LoRaWAN 1.0.2 (EU-868)
- Compatible with wireless M-Bus S1, C1/T1 modes (868 MHz) meters
- Compatible with Xylem Sensus RF Bubble Up (868 MHz)
- Compatible with Müller Funk (ME protocol, Walk-By) for µon and µflow skyW-2 and skyE-2
- RS-485 interface for connection to external M-Bus level converters
- Compatible with Relay PW100 M-Bus master level converter
- M-Bus load capacity defined by external converter (e.g. PW100)
- Internal memory, for over 64,000 telegrams
- Whitelist for up to 2,000 individual meters
- Remote configuration
- Signed firmware updates (FOTA) via mobile radio
Product Components
This product is manufactured by Lobaro using the components listed below. Detailed information about the firmware and other components can be found in their respective descriptions.
Please use the links provided to access comprehensive product details.
| Component | Manual / Description | Additional note |
|---|---|---|
| Firmware | app-nrf91-origin | See here for available firmware updates |
| Housing | LoCube | 122 mm (l) × 82 mm (w) × 55 mm (h) |
Power Supply | Battery | (Li-SOCl2) 3.6 V, 38 Ah |
| External power supply (12 V or 230 V) | Please contact | |
Optional Accessories | External Antenna (SMA) instead of | Please contact |
IP68 encapsulation with transparent, | ||
| LoCube Backplate Wall Mounting Kit | ||
| Pole Mounting Kit | ||
External M-Bus Level Converter | Relay PW100 (example) | Required for wired M-Bus operation via RS-485. |
Product Identification
- Name: Wireless M-Bus Gateway V4 MBus
- Type: LOB-GW4-MBUS
- MPN / Ordering code:
1200436
Datasheet & Quickstart
Please contact our sales team.
LED Signal Patterns
The device uses the standard V4 LED signal patterns. See LED Signal Patterns for the full reference.
Battery Lifetime Estimator
Please contact our sales team.
Configuration
The device is shipped with default configuration parameters. Local changes can be made via the config port using the USB Config Adapter and the Lobaro Config Tool.
For step-by-step instructions, see the Configuration Methods guides:
- 🔌 Local Config via USB — connect directly to the device
- 📡 Remote Config via CoAP — over NB-IoT / LTE-M via Lobaro Platform
- 📻 Remote Config via LoRaWAN — via LoRaWAN downlink
- 🔗 Remote Config via MQTT — for 3rd party MQTT backends
Custom factory configuration is available on request — devices can be pre-configured at production for your specific deployment. Contact sales@lobaro.de when ordering.
Configuration Parameters
This product runs the app-nrf91-origin firmware. To avoid duplication, the parameters are documented centrally with the firmware component and are not repeated here:
- Common firmware parameters — general, wireless M-Bus, LTE and LoRaWAN settings shared by all V4 gateways
- M-Bus Add-On parameters — wired M-Bus specific settings
- Temperature Add-On parameters — 1-Wire temperature sensor settings
Firmware Updates
The latest firmware can be found here:
- Download latest firmware
-
For further information on how to update the device, refer to: Firmware Update.
A remote firmware update over LoRaWAN is currently not possible.
LoRaWAN Uplink Formats
- LoRaWAN Protocol — Status Packet (Port 1) and wM-Bus uplink formats
- M-Bus Add-on LoRaWAN Uplinks
- 1-Wire / Temperature Add-on LoRaWAN Uplinks
Cellular Uplink (LTE)
Cellular uplink uses CoAP (with the Lobaro IoT Platform) or MQTT for third-party integration. The protocol details are documented centrally with the firmware:
The CoAP implementation details are not publicly disclosed and are intended for use exclusively with the Lobaro IoT Platform. If MQTT is not an option, please contact Lobaro directly.
Uplink Parser
A production-ready parser for the uplinks of this device is implemented within the Lobaro Platform. It covers the wireless M-Bus telegrams (including split telegram reassembly where applicable, AES-128 decryption for encrypted telegrams, and OMS-compliant data interpretation) as well as the add-on data of the respective variant, for example Modbus responses or sensor values.
Customers using the Lobaro Platform can utilize this parser directly as part of the platform processing pipeline.
If you are operating a Lobaro Gateway without using the Lobaro Platform, we can provide restricted platform access upon request. This allows you to inspect the parser behavior and use it as a technical reference for your own backend implementation.
Please contact our support team if you require access or further integration details.
Declaration of Conformity
| Download CE declaration of conformity |